Description
3-8
6ZB5 430–0BH02–1AA0
Siemens AG 1996 All Rights Reserved
SINUMERIK 805SM / 840C (BS)
3.2.3
Procedure for Installation and Startup
The following procedure is recommended for installation and startup of a
station with an IM 329-N, DP slave:
Set and check the following data on the module in accordance with
Section 2.1.1:
–
Control type
–
Address range (number of input and output bytes)
–
Base address
Install the module in the control:
–
Switch off the control
–
Plug the module into a valid slot, see information for the relevant
control in
Reference:
/3/, SINUMERIK 805SM,
Interface Description Part 2 – Connection Conditions
Reference:
/4/, SIROTEC ACR 20, Configuring Guide
Reference:
/5/, SINUMERIK 840C
Interface Description Part 2 – Connection Conditions
–
Set the station address on the front panel in accordance with
Section 2.1.2.
–
Connect the module to the SINEC L2-DP field bus
–
Switch on the control (POWER ON) and perform a RESTART of the
PLC if required
Note
On the SINUMERIK 840C, I/O modules that have just been slotted in are
not recognized until a cold RESTART of the control is performed.
Modify the configuration of the master (e.g. IM 308-B):
–
Add the configuration data of the new station to the existing program
file
–
For the IM 308–B: Write to the memory module
For the IM 329–N, master: perform DOWNLOAD
Reference:
/7/, SIROTEC ACR20, SINUMERIK 805SM/840C
Link to SINEC L2–DP with module IM 329–N
–
Program and activate monitoring and diagnostics functions on the
master and slave sides.
3.2 Description of the DP standard slaves