3
07.96
Description
3-23
Siemens AG 1996 All Rights Reserved 6ZB5 430–0BH02–1AA0
SINUMERIK 805SM / 840C (BS)
To configure the slave interface of the IM 328–N, select the screen form
“Configuring” in the field “Station type” of the type “ET 200U” (up to
COM ET 200 V3.x, use the type “IM 318–B”).
This sets the protocol for the IM 328–N to the SINEC L2–DP protocol up to
V3.x.
Note
Station No.:
Stations numbers 3 to 124 are allowed.
Station type:
The SINEC L2–DP slave module (IM 328–N) must be selected with the
configuration form of type ET 200U.
Station name:
You can enter a name for the station here (all keyboard characters are
allowed)
First free address:
The address of the first free byte is displayed for
DI
(digital inputs)
DQ (digital outputs)
Configuration field:
Depending on the address range, you can enter the following address
identifiers in these input fields:
8DE or 009
for 8 digital inputs
(1 IB)
8DA or 017
for 8 digital outputs
(1 QB)
011
for 16 digital inputs
(2 IB)
019
for 16 digital outputs
(2 QB)
for address range
4, 8 and 16 bytes
for address range
32 bytes
For an address range of 4, 8 or 16 bytes, first the address identifier 8DI
and then the address identifier 8DQ must be entered 4 times, 8 times or
16 times in the configuration field (or the corresponding decimal
number).
For an address range of 32 bytes, first the address identifier 011 and then
the address identifier 019 must be entered 16 times in the configuration
field.
Pressing the ENTER softkey stores the configuration data for this station
in the specified program file.
Configuration
3.3 Description of the L2-DP slave up to V3.x