3
07.96
Description
3-5
Siemens AG 1996 All Rights Reserved 6ZB5 430–0BH02–1AA0
SINUMERIK 805SM / 840C (BS)
3.2
Description of the DP standard slaves
Note
This section only applies if
The IM 328–N module is used with the order number:
6FC5012–0CA03–0AA0
and
The X999 jumper is assigned for operation as a SINEC L2–DP slave
(standard DP) (see Section 2.1.1).
3.2.1
Notes on parameterization of the slaves
Here are some notes that must be observed when the IM 328–N is used as a
standard slave in the ET 200 Distributed I/O System.
For example, the master IM 308–B or IM 329–N are used.
If the IM 308–B or IM 329–N module is the master
PG/PC with COM ET 200 (V4.x)
Type file for IM 328–N (see Section 3.1.1)
Note
About the system parameter BUS PROFILE:
Select the bus profile
“DP standard” or
“DP/FMS operation”
About the baud rate:
Baud rates up to 1500 kBaud are possible.
There is a separate configuration screen form to configure the slave interface
of the IM 328–N. To make this screen form available, the appropriate type
file must be installed (see Section 3.1).
Prerequisites
for slave para-
meterization
ET 200
system parameters
Configuration
3.2 Description of the DP standard slaves