07.96
Description
3-5
Siemens AG 1996 All Rights Reserved 6ZB5 430–0BH02–1AA0
SINUMERIK 805SM / 840C (BS)
Reference:
/5/, SINUMERIK 840C
Interface Description, Part 2 – Connection Conditions
((S. 2–7))
((Block 1))
Interface for slave
Via the interface X111 (SUB–D, socket, 9–way), the slave is connected to the
SINEC L2–DP field bus.
Note
TO connect up to the SINEC L2–DP field bus, the bus connectors with the
following order numbers are required:
Order number
Designation
SINEC L2 bus connector (degree of protection IP 20, without heavy–duty
thread socket)
SINEC L2 bus connector (degree of protection IP 20, with heavy–duty thread
socket)
For information about the bus cable and the bus connector see:
Reference: /1/, ET 200 Distributed I/O System Manual
((S. 2–9))
2.2
Hardware of the module
((Bildinschriften wie alte Vorlage, S. 2.1, mit folgenden zusätzlichen Inschrif-
ten: ))
für Slave = for slave
((Unterschrift))
Fig. 2–2 IM 328–N with the order number: ....
Note
This module has been superseded by the module .... .
((S. 2–10))
((Block 1))
Selecting the control system (S2.5, S2.6, S2.7 and S2.8)
The module can be used in the control systems listed. The control type must be
set with switches S2.5, S2.6, S2.7 and S2.8 as follows
((Tabelle: ))
geschlossen = closed
offen = open
((Block 2))
Note
The IM 328–N module can only be used for SINUMERIK 805SM in the cen-
tral controller.