2
07.96
Description
2-10
6ZB5 430–0BH02–1AA0
Siemens AG 1996 All Rights Reserved
SINUMERIK 805SM / 840C (BS)
2.2.1
Jumper settings
The module can be used in the control systems listed. The control type must
be set with switches S1, S5.1, S5.2 and S5.3 as follows:
S1
S5.1
S5.2
S5.3
SINUMERIK 805SM
closed
open
closed
open
SIROTEC ACR 20
closed
closed
closed
closed
SINUMERIK 840C
closed
closed
closed
closed
Note
The IM 328–N module can only be used for SINUMERIK 805SM in the
central controller.
Switches S2.1 and S2.2 must be set according to the table below in order to
set the address range of 4, 8, 16 or 32 input or output bytes.
Address range
S2.1 in position
S2.2 in position
4 bytes
open
open
8 bytes
closed
open
16 bytes
open
closed
32 bytes
closed
closed
Note
Address range of, for example, 4 bytes means that 4 input bytes and 4 output
bytes are available with the same base address.
The following switches are used to set the base address:
S3.1 to S3.8
for an address range of
4 bytes
S3.2 to S3.8
for an address range of
8 bytes
S3.3 to S3.8
for an address range of
16 bytes
S3.4 to S3.8
for an address range of
32 bytes
Selecting the
control system
(S1, S5.1, S5.2 and
S5.3)
Setting of address
range (number of
input and output
bytes) (S2.1 and
S2.2)
Setting the base
address
(S3.1 to S3.8)
2.2 Hardware of the module 6FC5 012–0CA01–0AA0