3
07.96
Description
3-7
Siemens AG 1996 All Rights Reserved 6ZB5 430–0BH02–1AA0
SINUMERIK 805SM / 840C (BS)
3.2.2
Configuration example for slave
The text below describes the configuration data for integrating a slave
IM 328-N into an already existing ET 200 distributed I/O system.
The configuration data are stored in the program file C:[email protected].
Slave stations exist with station numbers 3 and 4.
A SIMATIC S5-115U is available as master PLC (linear addressing, I/O
range = P, 256 input and ouput bytes).
Configuration data of a new station:
Station address and name:
5, example for IM 328–N slave
First available address:
DI: 96, DQ: 96
Address range = 4 bytes
⇒
Address identifier = 51
(see Section 3.2.1)
Based on the above assumptions, the CONFIGURING screen form must be
parameterized as follows:
Program file selected C: [email protected]
0.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
51
F1
STATION
+
DELETE
STATION
STATION
–
NEW
STATION
ADRESS
ASSIGNM.
ENTER
HELP
EXIT
F2
F3
F4
F5
F6
F7
F8
Station No.:
Area:
Station type:
Station name:
SIMATIC S5 / COM ET 200
First available address:
Configuration:
DI: DQ: AI: AQ:
5
P
96
96
Module address:
I:
Q:
CONFIGURING
Example for IM 328–N Slave
IM 328–N slave DP
Fig. 3-2
CONFIGURING screen form
Assumptions
3.2 Description of the DP standard slaves