Description | 3
17/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Fig. 9:
Cable connection for ring-main feeder (example)
Tab. 5:
Possibilities of connection
Cable
Panel width [mm]
310
430
500
Thermoplastic-insulated
single-core cable
1 cable per phase
X
X
X
1 cable per phase
with surge limiter or surge arrester
O
O
O
with voltage transformer 4MT8
–
–
O
2 cables per phase
O
O
O
2 cables per phase
with surge limiter or surge arrester
O
O
O
Thermoplastic-insulated
three-core cable
1 cable
on request
Paper-insulated mass-im-
pregnated cable
1 cable
on request
X
Standard
O
Option
Option
▪ Mounted cable clamps on cable bracket
▪ Deep cable compartment cover
▪ Cable testing, e.g. with measuring bolt, [
3.8.2 Cable connection for transformer feeders
For the cable connection, customary cable plugs for interface type A with plug-in contact
(standard), or interface type C with bolted contact M16 (option) are used according to
EN 50181/DIN EN 50181.
Available designs:
▪ Screened (conductive) design (standard)
▪ 1 cable per phase
Recommended cable plugs:
▪ Interface type C [
Page 18, "Cable plugs for single cable connection (interface type C)"].
▪ Interface type A and possible connection cross-sections, [
Page 20, "Cable plugs for single
cable connection (interface type A)"].
The installation of other makes and types is possible on request.
▪
Option:
Mounted cable clamps on cable bracket
Summary of Contents for 8DJH