Operation | 9
163/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
9.10 Cable testing
9.10.1 Cable testing via cable plugs
DANGER
Mortal danger due to non-interlocked switch-disconnector
If the cable compartment cover is removed, the switch-disconnector is not interlocked
during the cable test. Switching to CLOSED position can cause an internal arc or an electric
shock.
⇨ Observe the Five Safety Rules.
⇨ Fit switching prohibition signs.
⇨ Padlock the locking device (option).
WARNING
Mortal danger due to overvoltages
Cable testing with connected cables represents a special stress for the isolating distance. If
the busbar of the switchgear under test or the opposite substation are live with operating
voltage, no overvoltages may occur.
⇨ Overvoltages must be avoided by suitable measures taken by the switchgear operator.
NOTICE
High test voltage
The test voltage can damage connection cables, cable plugs and voltage detecting systems.
⇨ Observe the manufacturer information related to the connection cables, cable plugs and
voltage detecting systems (maximum test values).
a
d
s
g
h
f
1
Bushing
2
Measuring bolt
3
Test lead
4
Earthing connection of cable shield
5
Earthing connection of plug
6
T-plug
Tab. 52:
Test voltages
Rated voltage of
switchgear
Test voltage
AC test voltage VLF
1)
0.1 Hz
AC
DC
Rectangle
Sinus
Test dura-
tion
U
ct
Test dura-
tion
U
ct
Test dura-
tion
Mean value
Maximum
value
Mean value
Maximum
value
[kV]
[kV]
[min]
[kV]
[min]
[kV]
[kV]
[kV]
[kV]
[min]
7.2
11
1
22
15
22
22
15.6
22
60
12
19
1
38
15
38
38
26.8
38
60
15
28
1
52
15
52
52
36.8
52
60
17.5
28
1
52
15
52
52
36.8
52
60
24
38
1
72
15
72
72
51
72
60
1)
Very low frequency
1. Disconnect the feeder under test.
2. Make sure that the feeder in the opposite substation has also been isolated and secured
against reclosing.