4 | Technical data
40/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
Transformer
HV HRC fuse-link
S
r
[kVA]
u
K
[%]
I
r
[A]
I
r
[A]
U
r
[kV]
e [mm]
Order number
Make SIBA
Make Mersen
250
4
43.74
63
3…7.2
292
30 099 13.63
–
80
3…7.2
292
30 099 13.80
–
System operating voltage U
n
4.16…4.8 kV
20
4
2.78
6.3
3…7.2
292
30 098 13.6,3
–
30
4
4.16
10
3…7.2
292
30 098 13.10
–
50
4
6.93
16
3…7.2
292
30 098 13.16
–
75
4
10.4
16
3…7.2
292
30 098 13.16
–
20
3…7.2
292
30 098 13.20
–
100
4
13.87
20
3…7.2
292
30 098 13.20
–
25
3…7.2
292
30 098 13.25
–
125
4
17.35
25
3…7.2
292
30 098 13.25
–
31.5
3…7.2
292
30 098 13.31,5
–
160
4
22.2
31.5
3…7.2
292
30 098 13.31,5
–
40
3…7.2
292
30 098 13.40
–
200
4
27.75
40
3…7.2
292
30 098 13.40
–
50
3…7.2
292
30 098 13.50
–
250
4
34.7
50
3…7.2
292
30 098 13.50
–
63
3…7.2
292
30 099 13.63
–
315
4
43.7
63
3…7.2
292
30 099 13.63
–
80
3…7.2
292
30 099 13.80
–
System operating voltage U
n
5.0…5.5 kV
20
4
2.3
6.3
3…7.2
292
30 098 13.6,3
–
30
4
3.4
6.3
3…7.2
292
30 098 13.6,3
–
10
3…7.2
292
30 098 13.10
–
50
4
5.7
10
3…7.2
292
30 098 13.10
–
16
3…7.2
292
30 098 13.16
–
75
4
8.6
16
3…7.2
292
30 098 13.16
–
20
3…7.2
292
30 098 13.20
–
100
4
11.5
16
3…7.2
292
30 098 13.16
–
20
3…7.2
292
30 098 13.20
–
125
4
14.4
20
3…7.2
292
30 098 13.20
–
25
3…7.2
292
30 098 13.25
–
160
4
18.4
31.5
3…7.2
292
30 098 13.31,5
–
40
3…7.2
292
30 098 13.40
–
200
4
23
40
3…7.2
292
30 098 13.40
–
50
3…7.2
292
30 098 13.50
–
250
4
28.8
40
3…7.2
292
30 098 13.40
–
50
3…7.2
292
30 098 13.50
–
315
4
36.3
50
3…7.2
292
30 098 13.50
–
63
3…7.2
292
30 099 13.63
–
400
4
46.1
63
3…7.2
292
30 099 13.63
–
80
3…7.2
292
30 099 13.80
–
System operating voltage U
n
6…7.2 kV
20
4
1.9
6.3
6…12
292
30 004 13.6,3
–
6.3
3…7.2
292
30 098 13.6,3
–
6.3
6…12
442
30 101 13.6,3
–
50
4
4.8
10
3…7.2
292
30 098 13.10
–
10
6…12
292
30 004 13.10
–
10
6…12
442
30 101 13.10
–
16
3…7.2
292
30 098 13.16
–
16
6…12
292
30 004 13.16
45DB120V16PTD
16
6…12
442
30 101 13.16
–