4 | Technical data
34/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
Tab. 30:
Internal arc classification IAC (option)
Type of installation of the switchgear
IAC class
Wall-standing arrangement
IAC A FL 21 kA 1 s
Free-standing arrangement
IAC A FLR 21 kA 1 s
IAC
Internal Arc Classification
F
Front
A
Type of accessibility: Switchgear in closed electrical service lo-
cation, access "for authorized personnel only".
L
Lateral sides
R
Rear
[kA] Arc test current
[s]
Test duration
4.7 Standards and guidelines
The switchgear complies with the following prescriptions and standards:
IEC/EN standard
VDE standard
Switchgear
62271-1
0671-1
62271-200
0671-200
Devices
Circuit-breakers
62271-100
0671-100
Disconnectors
62271-102
0671-102
Earthing switches
Switch-disconnectors
62271-103
0671-103
Switch-fuse combination
62271-105
0671-105
HV HRC fuses
60282-1
0670-4
Voltage detecting systems
61243-5
0682-415
Surge arresters
60099
0675
Degree of protection
60529
0470-1
Insulation
60071
0111
Instrument trans-
formers
Current transformers
61869-1/-2
0414-9-1/-2
Voltage transformers
61869-1/-3
0414-9-1/-3
Electronic current transformers
61869-8
0414-44-8
Electronic voltage transformers
61869-7
0414-44-7
Insulating gas SF
6
60376
0373-1
Installation and erection
61936-1
HD637-S1
0101
Environmental conditions
60721-3-3
DIN EN 60721-3-3
Type approval of vacuum interrupter
The vacuum interrupters fitted in the switching devices are type-approved in accordance with
§ 45 of the Radiation Protection Act (StrlSchG) of the Federal Republic of Germany as
interference radiators, and they meet the requirements for interference radiators according to
§ 23 of the latest Radiation Protection Ordinance (StrlSchV) up to the rated voltage specified in
the approval document.
Vacuum interrupters featuring type approval may be operated by the owner of the switchgear
without explicit authorization. The approval document is available on request specifying the
switchgear type and factory reference number.
Electromagnetic compatibility (EMC)
The a.m. standards as well as the "EMC Guide for Switchgear"
[1]
are applied during design,
manufacture and erection of the switchgear. Installation, connection and maintenance have to
be performed in accordance with the stipulations of the operating instructions.
For operation, the legal stipulations applicable at the place of installation have to be observed
additionally. In this way, the switchgear assemblies of this type series fulfil the basic protection
requirements of the EMC guide.
[1]
Dr. Bernd Jäkel, Ansgar Müller, "Medium-Voltage Systems – EMC Guide for Switchgear", Siemens AG 2012