Annex | 12
169/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Tab. 53:
Fault coding MCU-MH and MCU-MH-MOD
Type of fault
LED status
indicator
Interlocking to cir-
cuit-breaker
1)
Cause
Measure
Incorrect sense of rotation
of motor
Lights up per-
manently red
OPEN
Motor polarity interchanged
▪ Check motor connecting leads
▪ Carry out a reset of the MCU
Relay on MCU clocks on
command input (approx. 1x
per sec.)
No indication
OPEN
No load voltage available
▪ Check the load voltage supply
Relay on MCU clocks very
quickly on command input
(approx. 5x per sec.)
No indication
OPEN
No control voltage available
▪ Check the control voltage supply
H-bridge is not isolated from
supply
Flashes 2x red
CLOSED
N
2)
not earthed (IT system)
▪ Earth N.
▪ Carry out a reset of the MCU
Load voltage relay of MCU defective
▪ Replace MCU
No feedback of
disconnector contact after
disconnector CLOSED com-
mand
Flashes 3x red
CLOSED
Disconnector could not be CLOSED
within the maximum permissible run-
time. Mechanical defect or defect at the
gear motor
▪ Check operating mechanism and
gear motor
▪ Switch the operating mechanism
manually to an end position and
perform reset
No feedback of opening
contact after
disconnector OPEN com-
mand
Flashes 4x red
CLOSED
Disconnector could not be OPENED
within the maximum permissible run-
time. Mechanical defect or defect at the
gear motor
▪ Check operating mechanism and
gear motor
▪ Switch the operating mechanism
manually to an end position and
perform reset
No feedback of earthing
switch contact after earth-
ing switch CLOSED com-
mand
Flashes 5x red
CLOSED
Earthing switch could not be CLOSED
within the maximum permissible run-
time. Mechanical defect or defect at the
gear motor
▪ Check operating mechanism and
gear motor
▪ Switch the operating mechanism
manually to an end position and
perform reset
No feedback of opening
contact after earth-
ing switch OPEN command
Flashes 6x red
CLOSED
Earthing switch could not be OPENED
within the maximum permissible run-
time. Mechanical defect or defect at the
gear motor
▪ Check operating mechanism and
gear motor
▪ Switch the operating mechanism
manually to an end position and
perform reset
No standby mode after end
of command
Flashes 8x red
CLOSED
Circuit for automatic shutdown of MCU
defective
▪ Replace MCU
Impermissibly long switch-
ing command
Flashes 8x red
CLOSED
Switching command is applied for more
than 5 min
▪ Shorten command output
▪ Carry out a reset of the MCU
1)
Off = circuit-breaker can be switched, On = circuit-breaker cannot be switched
2)
Neutral conductor
Tab. 54:
Fault coding MCU-RI
Type of fault
LED status indicator
Cause
Measure
Incorrect sense of rotation of motor Lights up permanently
red
Motor polarity interchanged
▪ Check motor connecting leads
▪ Carry out a reset of the MCU
Relay on MCU clocks on command
input (approx. 1x per sec.)
No indication
No load voltage available
▪ Check the load voltage supply
Relay on MCU clocks very quickly
on command input (approx. 5x per
sec.)
No indication
No control voltage available
▪ Check the control voltage supply
No feedback of disconnector con-
tact after disconnector CLOSED
command
Flashes 3x red
Disconnector could not be CLOSED within the
maximum permissible runtime.
▪ Mechanical defect or defect at the gear
motor
▪ Check operating mechanism and
gear motor
▪ Carry out a reset of the MCU
No feedback of opening contact af-
ter disconnector OPEN command
Flashes 4x red
Disconnector could not be switched to OPEN
position within the maximum permissible run-
time.
▪ Mechanical defect or defect at the gear
motor
▪ Check operating mechanism and
gear motor
▪ Carry out a reset of the MCU
No standby mode after end of com-
mand
Flashes 8x red
Circuit for automatic shutdown of MCU defec-
tive
▪ Replace MCU
Impermissibly long switching com-
mand
Flashes 8x red
Switching command is applied for more than
5 min
▪ Shorten command output
▪ Carry out a reset of the MCU