Installation | 7
105/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
3. Push the surge arrester plate
3
between the hexagon nuts of the adapter feet, and tighten.
Use hexagon nuts M12
2
with conical spring washers
4
.
Fig. 126:
Mounting the surge arrester plate
4. Fasten the upper cross member with 4 self-tapping bolts M6
1
.
5. Fasten the surge arrester plate with 2 hexagon head bolts M8x16 % and plain washers
6
to
the upper cross member.
Fig. 127:
Mounting the upper cross member
Fig. 128:
Fastening the surge arrester plate
6. Earth the cable shields with cable lugs and earthing bolts M10 at the upper cross member.
Fig. 129:
Earthing the cable shields
1
Cable shield, phase L1
2
Cable shield, phase L2
3
Cable shield, phase L3
4
Upper cross member
7. Observe the minimum distances according to the manufacturer's instructions while
connecting non-screened cable plugs or surge arresters.
The use of RICS5xxx cable plugs with RDA in panels with a width of 310 mm is allowed
under normal ambient conditions according to IEC 62271-1 despite the reduced distance.
✓
The installation of the Raychem RICS5xxx cable plug with RDA is completed.