7 | Installation
80/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
Lining up the panel
1. Approach the panel to be lined up to the fixed-mounted panel.
Fig. 83:
Lining up the panel
1
Right-hand panel
2
Vessel adapter for right-hand
panel (option)
3
Nut-and-washer assembly M8
(4x)
4
Bolt-and-washer assembly
M8x45 (4x)
5
Vessel adapter for left-hand
panel (option)
6
Left-hand panel
2. Interconnect the panels with 4 panel connecting bolts (bolt-and-washer assemblies M8x40)
at the upper panel connection,
but do not bolt tight yet
.
3. If required, bolt the vessel adapter tight between the two panels.
4. Bolting panels together [
Page 80, "Bolting panels together"]
7.15.3 Bolting panels together
INFORMATION
Setnuts may be fastened at the bolted joints in the left-hand panel.
⇨ Remove the setnuts before bolting the panels together.
1. Tighten the 6 panel connecting bolts
1
uniformly together with the bolt-and-washer
assemblies at the clamping plate
2
until both panels are joined without any gaps
(tightening torque: 30 Nm).
2. Screw each of the bolt-and-washer assemblies from the left-hand panel to the right-hand
panel into the setnuts provided for this purpose. Make sure that there is a uniform distance
between the panels.
30 Nm
6x
Fig. 84:
Bolted joints for the panel interconnection
1
Bolt-and-washer assemblies
M8x20 (6x)
2
Bolt-and-washer assemblies
M8x45 at the clamping plate
(2x or 4x)
3
Bolt together only in circuit-
breaker panel type 1.1
4
Bolt together in all panel types
except for circuit-breaker panel
type 1.1
Bolted joint