PSU2412 Additional Circuit Breaker Installation Instructions  

 

LT0560 Issue 1.0 

14 May 2012 

Page 1 of 4 

     

         

PSU2412 Additional Circuit Breaker Kit (KT0546) 

 

Installation Instructions

 

General Description 

The PSU2412 Additional Circuit Breaker Kit is used to add another Circuit Breaker to a VIGILANT PSU2412 Power 
Supply.  Up to two kits may be fitted. 

These instructions cover the fitting and connection of the Circuit Breaker. They do not cover details of any 
necessary changes to the system configuration or other hardware.  

 
Contents of this Kit 

Item 

Qty 

Description 

LB0642 

Label For New Circuit Breaker Lead (two pre-printed, one blank) 

LM0133 

Loom, Red Auto 158, 250mm long, M4 Lug to M5 Lug. 

LM0136 
LM0390 


Loom, Red Auto 158, 1725mm long, M5 Lug one end. 
Loom, Black Auto 158, 1500mm long, M4 Lug one end. 

LT0560 

These Installation Instructions. 

SC0189 

Machine Screw, PH Pozi, 6/32 UNC x 1/4 long, ZP. 

SU0099 

Cable Tie Holder, Adhesive Based. 

SW0142 

Circuit Breaker, DC, 50A, 65V. 

WA0032 

Washer, Flat, 1/8 ZP. 

 
 
 

Circuit Breaker Installation 

Follow these steps to install an additional Circuit Breaker in a PSU2412. 
 
1.  Unplug the PSU2412 from mains power. 
2.  Remove the PSU2412 from the rack cabinet. 
3.  Remove the PSU2412 cover. 
4.  Remove screws, nuts, washers and rubber bung from the spare Circuit Breaker position where you intend to fit 

the additional Circuit Breaker (see Figure 1).  These are no longer required. 

 

Figure 1 

– Location of additional Circuit Breaker position(s) 