7 | Installation
84/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
4. Hook the busbar termination cover into the clamping plate at the top, and fasten it
(tightening torque: 30 Nm).
Fig. 90:
Hooking in the busbar termination
cover
Fig. 91:
Mounting the busbar termination
cover
1
Busbar termination cover
2
Bolt-and-washer assembly M8x30
3
Nut-and-washer assembly M8
5. Insert the cap into the opening of the side wall.
1
Cap
Mounting the closure plate
If the panel was not originally supplied as an end panel, a closure plate must be mounted on the
side walls in the cable compartment.
1.
If an earthing point is mounted on the side wall:
Remove the earthing point
2
.
2. Fasten the closure plate
1
to the side wall using 2 blind rivets
3
.
Observe the mounting
position of the closure plate (see arrow)
.
3. Mount the removed earthing point
2
again at the same position on the closure plate.
Fig. 92:
Closure plate with earthing point
Fig. 93:
Closure plate at the panel with
earthing busbar
1
Closure plate
2
Earthing point
3
Blind rivet M5x12
Completing installation
1. Depending on the position of the end panel, close the openings with sealing stoppers or
bolt-and-washer assemblies.