Technical data | 4
31/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Operating times, contacts
The time indications in the following table refer to the application of the switchgear in
accordance with IEC 60721-3-3 Class 3K4. If the switchgear is operated beyond this range, the
indicated times may deviate.
Tab. 24:
Operating times
Designation
Component (item designation)
Unit
Time
Type 1.1
Type 2
Closing time
Closing solenoid
(-Y9)
ms
< 75
< 30
Opening time
1st shunt release
(-Y1)
ms
< 65
< 35
Additional release
2nd shunt release
(-Y2)
ms
< 50
—
(-Y3)
ms
—
< 35
C.t.-operated release
(-Y4)
ms
< 50
—
(-Y6)
ms
--
< 35
Undervoltage release
(-Y7)
ms
< 50
< 35
Low-energy release
(-Y6)
ms
—
< 35
Arcing time
ms
< 15
< 15
Break time
1st shunt release
(-Y1)
ms
< 80
< 50
Additional release
2nd shunt release
(-Y2)
ms
< 65
—
(-Y3)
ms
—
< 50
C.t.-operated release
(-Y4)
ms
< 65
--
(-Y6)
ms
—
< 50
Undervoltage release
(-Y7)
ms
< 65
< 50
Low-energy release
(-Y6)
ms
—
< 50
Charging time (motor)
s
< 15
< 15
Dead time
s
0.3
180
Close-open contact time
1st shunt release
(-Y1)
ms
< 80
< 65
Additional release
2nd shunt release
(-Y2)
ms
< 60
—
(-Y3)
ms
—
< 65
C.t.-operated release
(-Y4)
ms
< 60
—
(-Y6)
ms
—
< 65
Undervoltage release
(-Y7)
ms
< 60
< 65
Low-energy release
(-Y6)
ms
—
< 65
Minimum command duration
1)
CLOSE
Closing solenoid
(-Y9)
ms
45
40
OPEN
1st shunt release
(-Y1)
ms
< 40
< 40
Additional release
2nd shunt release
(-Y2)
ms
< 20
--
(-Y3)
ms
--
< 40
C.t.-operated release
(-Y4)
ms
< 20
--
(-Y6)
ms
--
< 20
Undervoltage release
(-Y7)
ms
< 20
< 20
Low-energy release
(-Y6)
ms
--
< 20
1)
For operation of the switchgear beyond the range defined by IEC 60721-3-3 Class 3K4, a minimum command duration of 100 ms is
recommended.
Closing time:
The interval of time between the initiation (command) of the closing operation
and the instant when the contacts touch in all poles.
Opening time:
The interval of time between the initiation (command) of the opening operation
and the instant when the contacts separate in all poles.
Arcing time:
The interval of time from the first initiation of an arc and the instant of final arc
extinction in all poles.
Break time:
The interval of time between the initiation (command) of the opening operation
and the instant of final arc extinction in the last-pole-to-clear (= opening time and arcing time).
Close-open contact time:
The interval of time - in a make-break operating cycle - between the
instant when the contacts touch in the first pole in the closing process, and the instant when the
contacts separate in all poles in the subsequent opening process.