9 | Operation
152/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
Circuit-breaker with automatic reclosing (AR)
In order to ensure the operating sequence O - 0.3 s - CO for automatic reclosing of a circuit-
breaker with automatic reclosing feature (AR), recharge the closing spring manually again after
closing.
9.7.2 Closing circuit-breaker type 1.1
☒ Circuit-breaker in OPEN position
☒ Three-position disconnector in CLOSED position
☒ "Spring charged" indicator shows "spring charged"
☒ Auxiliary voltage applied at the undervoltage release
(option)
0000
2. Actuate the ON pushbutton.
✓ The position indicator of the circuit-breaker is in
CLOSED position.
✓
The "spring charged" indicator shows "spring not
charged".
✓
If the panel is equipped with a motor operating
mechanism, the spring energy store is automatically
charged again after a few seconds. Then, the "spring
charged" indicator shows "spring charged" again.
0000
9.7.3 Opening circuit-breaker type 1.1
☒ Circuit-breaker in CLOSED position
☒ Three-position disconnector in CLOSED position
☒ Auxiliary voltage applied at the undervoltage release
(option)
0000
2. Actuate the OFF pushbutton.
✓ The position indicator of the circuit-breaker is in
OPEN position.
✓
The "spring charged" indicator shows "spring not
charged".
✓
If the panel is equipped with a motor operating
mechanism, the spring energy store is automatically
charged again after a few seconds. Then, the "spring
charged" indicator shows "spring charged" again.
0000
9.7.4 L1.1: Switching the three-position disconnector from OPEN to CLOSED position
☒ Circuit-breaker in OPEN position
☒ Three-position disconnector in OPEN position
1. Check service readiness [
2. Remove the padlock (optional) from the locking
device.
0000