9 | Operation
134/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
9.2 Indicators and control elements
R
Ort
Fern
SIEMENS
R
T
Fig. 172:
RRT panel block
1
Rating plate
10
ON pushbutton for transformer feeder
2
Short-circuit indicator, earth-fault indicator, integrated
capacitive voltage detecting system (option)
11
Feeder designation label
3
ON/OFF momentary-contact rotary control switch for
motor operating mechanism (option)
12
Actuating opening for "spring charging"
4
Local-remote switch for motor operating mechanism
(option)
13
Actuating opening for CLOSING/OPENING the earthing
switch
5
Ready-for-service indicator
14
"Fuse tripped" indicator
6
Position indicator for disconnector
15
Actuating opening for CLOSING/OPENING the
disconnector
7
Key-operated interlock (option)
16
Position indicator for earthing switch
8
OFF pushbutton for transformer feeder
17
Locking device
9
"Spring charged" indicator
18
Sockets for capacitive voltage detecting system
0000
SIEMENS
L2
Fig. 173:
Circuit-breaker panel type L2
1
Ready-for-service indicator
2
ON pushbutton for circuit-breaker
3
Actuating opening for disconnector
4
Position indicator for disconnector
5
Three-position switch-disconnector locking device
6
Padlock (option)
7
Actuating opening for earthing switch
8
Position indicator for earthing switch
9
Circuit-breaker locking device
10
Actuating opening for "spring charging"
11
Position indicator for circuit-breaker
12
Operations counter
13
OFF pushbutton for circuit-breaker
14
"Spring charged" indicator
Summary of Contents for 8DJH
Page 173: ......