7 | Installation
78/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
Lining up the panel
NOTICE
Polluted silicone coupling
A polluted silicone coupling can cause an internal arc during operation and damage the
switchgear.
⇨ Clean the grease and pollution off the insertable sleeves and push-on surfaces of the
silicone couplings.
1. Apply the supplied mounting paste to the push-on surfaces of the silicone couplings evenly,
thinly and all around.
Fig. 78:
Applying mounting paste to the silicone couplings
2. Push the panel to be lined up to the fixed-mounted panel.
3. Thread the guiding tension bolts
1
into the clamping plate in the panel to be lined up, until
the distance
2
between the two panels is approx. 30 mm.
Fig. 79:
Lining up the panel
Fig. 80:
Guiding tension bolt threaded in
1
Guiding tension bolt
2
Distance approx. 30 mm