Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 9 of 50
1.2.2 AC Current
Nominal
Measuring Range
In
1, 5 A Phase and earth
80 x
In
fn
50, 60Hz
47 to 62Hz
Note. 1 A and 5 A nominal inputs are user selectable on each model.
1.2.2.1
Burden
1.2.2.2
Thermal Withstand
Overload Period
Current
Phase and Earth
1A
5A
Continuous
3.0
x In
10 minutes
3.5
x In
5 minutes
4.0
x In
3 minutes
5.0
x In
2 minutes
6.0
x In
3 seconds
57.7A
202A
2 seconds
70.7A
247A
1 second
100A
350A
1 cycle
700A
2500A
Attribute
Value - Phase and Earth
1A
5A
AC Burden
0.1 VA
0.3 VA