Chapter 4 - 7SR242 Duobias · Data Communications Definitions
© 2015 Siemens Protection Devices Limited
Chapter 4 - Page 19 of 92
3. IEC 60870-5-103 Definitions
3.1 Introduction
This section describes the IEC 60870-5-103 protocol implementation in the relays. This protocol is used for the
communication with Reydisp software and can also be used for communication with a suitable control system.
The control system or local PC acts as the master in the system with the relay operating as a slave responding
to the master's commands. The implementation provides event information, time synchronising, commands and
measurands and also supports the transfer of disturbance records.
This protocol can be set to use any or all of the relays hardware interfaces (USB, Fibre Optic, RS232, RS485 and
Ethernet) and is the standard protocol used by the USB port. The relay can communicate simultaneously on all ports
regardless of protocol used.
The Station Address of the port being used must be set to a suitable address within the range 0 - 254 to enable
communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting.
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......