Chapter 5) 7SR242 Duobias Installation Guide
©2015 Siemens Protection Devices Limited
Chapter 5 Page 20 of 24
6.3 Optional Fibre Optic Connections
Where fitted rear Data Comms ports 3 and 4 comprise Fibre–Optic ST™ (BFOC/2.5) bayonet connectors-4 per
product. 62.5 / 125 m glass fibre is recommended for all lead lengths.
When installing fibre, ensure that the fibres’ bend radii comply with the recommended minimum for the fibre used-
typically 50mm is acceptable.
The fibre optic data comms link will be interrupted if the relay element is withdrawn from the case.
Computer or
Control System
Sigma 1
Tx
Rx
Tx
Rx
62.5/125
µm
fibre optic
with ST connectors
Tx
Rx
Tx
Rx
Tx
Rx
Tx
Rx
Tx
Rx
Tx
Rx
Master
To
Control
System
USB or 9 pin male
D connector
RS232 straight
Through cable
25 pin male
D connector
Figure 6.3-1 Data Comms to Multiple Devices Using Sigma 1 and F.O. Star Network
Figure 6.3-2 Data Comms to Multiple Devices Using Sigma 3 and F.O. Ring Network
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......