Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 15 of 50
1.4 Environmental Performance
1.4.1 General
1.4.1.1
Temperature
IEC 60068-2-1/2
Type
Level
Operating range
-10 C to +55 C
Storage range
-25 C to +70 C
1.4.1.2
Humidity
IEC 60068-2-78
Type
Level
Operational test
56 days at 40 C and 93 % relative humidity
1.4.1.3
Transient Overvoltage
IEC 60255-5
Type
Level
Between all terminals and earth, or
between any two independent circuits
5.0 kV, 1.2/50 s 0.5j
1.4.1.4
Insulation
IEC 60255-5
Type
Level
Between any terminal and earth
2.0 kV AC RMS for 1 min
Between independent circuits
Across normally open contacts
1.0 kV AC RMS for 1 min
1.4.1.5
Enclosure Protection
IEC 60529
Type
Level
Installed with cover on
IP 51 from front
Installed with cover removed
IP 20 from front