Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide
©2015 Siemens Protection Devices Limited
Chapter 6 Page 38 of 62
Phase
Is
(Amps)
DTL
(sec)
P.U. Current
Amps
Operate Time
0.5 x Is
NOTES
Wn-I
L1
(I
A
)
Wn-I
L2
(I
B
)
Wn-I
L3
(I
C
)
Wn-I
L1
(I
A
)
Wn-I
L2
(I
B
)
Wn-I
L3
(I
C
)
Elements can be blocked by operation of a Binary Input Inhibit or by operation of the 37-n U/I Guard element.
This functionality should be checked.
Element BI Inhibits U/I
Guard
NOTES
37-1
37-2
Check correct indication, trip output, alarm contacts, waveform record.
2.7.2
37G-n Elements
Apply current to the I
Gn
input at a level above the 37G-n setting until the element resets.
If DTL setting is small, gradually reduce current until element operates.
If DTL is large apply 1.1x setting, check for no operation, apply 0.9x setting, check operation
Apply 0.5x setting current and record operating time
Phase
Is
(Amps)
DTL
(sec)
P.U. Current
Amps
Operate Time
0.5 x Is
NOTES
I
G
I
G
Elements can be blocked by operation of a Binary Input Inhibit.
This functionality should be checked.
Element BI Inhibits
NOTES
37G-1
37G-2
Check correct indication, trip output, alarm contacts, waveform record.
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......