Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 43 of 50
2.15 81Under/Over Frequency
2.15.1 Reference
Parameter
Value
F
s
Setting
40, 40.01… 69.99 Hz
Hyst
Hysteresis setting
0, 0.1… 80%
td
Delay setting
0.00, 0.01… 20.0, 20.1… 100.0, 101.…1000, 1010 … 10000 ,
10100 … 14400 s
2.15.2 Operate and Reset Level
Attribute
Value
F
op
Operate level
100 %
F
s
, 10mHz
Reset level
overfrequency
(100 % -
hyst
)
xF
op,
10mHz
underfrequency
(100 % +
hyst
)
xF
op,
10mHz
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
2.15.3 Operate and Reset Time
Attribute
Value
t
basic
Element basic
operate time
(for ROCOF
between 0.1
and 5.0 Hz/sec)
overfrequency
Typically 110ms
Maximum 150ms
underfrequency
Typically 110ms
Maximum 150ms
t
op
Operate time following delay
t
basic
+
t
d
, 1 % or 10ms
Repeatability
1 % or 10ms
Disengaging time
100 ms
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......