Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide
©2015 Siemens Protection Devices Limited
Chapter 6 Page 32 of 62
2.5
Open Circuit (46BC)
Figure 2-7 Open Circuit
Voltage Inputs:
n/a
Current Inputs:
W1-I
L1
(I
A
), W1-I
L2
(I
B
), W1-I
L3
(I
C
), or W2-I
L1
(I
A
), W2-I
L2
(I
B
), W2-I
L3
(I
C
),
Disable:
51N, 46IT, 46DT
Map Pickup LED:
46BC - Self Reset
This function uses the ratio of NPS current to PPS current to detect an open circuit . These quantities can be
produced directly from many advanced test sets but with limited equipment the following approach can be
applied.
Apply 3P balanced current with normal phase rotation direction. This current will consist of PPS alone, no NPS or
ZPS.
Increase 1 phase current magnitude in isolation to produce NPS. The single phase unbalance current will contain
equal quantities of ZPS, NPS and PPS. The NPS component will be 1/3 of the unbalance current and the total
PPS component will be value of the original balanced 3P current plus 1/3 of the additional unbalance current. i.e.
as the single phase unbalance current increases, the ratio of NPS to PPS will also increase. The levels of each
sequence component current can be monitored in the
Current Meters
in
Instruments Mode
.
Inject 1A of balanced current. Gradually increase imbalance current, operating level should be as follows:
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......