7SR242 Duobias Technical Manual
Chapter 4 - Page 14 of 92
© 2015 Siemens Protection Devices Limited
Setting Name
Range/Options
Default
Setting
Notes
COM3
Protocol
OFF
IEC60870-5-103
MODBUS-RTU
DNP3
IEC60870-5-103
The protocol used
to communicate on
the standard RS485
connection.
COM3
Station
Address
0 - 254 for IEC60870-5-103
1 - 247 for Modbus RTU
0 - 65534 for DNP3.0
0
An address within the
range of the relevant
protocol must be
given to identify the
relay. Each relay in a
network must have a
unique address.
COM3
Baud Rate
75 110 150 300
600 1200 2400 4800
9600 19200 38400
57600 115200
19200
The baud rate set
on all of the relays
connected to the
control system must
be the same as the
one set on the master
device.
COM3
Parity
NONE
ODD
EVEN
EVEN
The parity set on
all of the relays
connected to the
control system must
be the same and in
accordance with the
master device.
COM3
Line Idle
LIGHT ON
LIGHT OFF
LIGHT OFF
LIGHT OFF
Not applicable for
RS 485 or RS 232
option, set to OFF.
COM3
Data Echo
#1
ON
OFF
OFF
OFF
Not applicable for
RS 485 or RS 232
option, set to OFF.
COM3
Mode
Local
Local or Remote
Remote
Remote
, for
further explanation
COMMS MODULE
IRIG-B
COM3
GND
TERM
B
A
Laptop computer
RS232 straight
through cable
USB or 9 pin male
D connector
RS485 Screened
twisted pair
7SR24
Fig. 2-5 Additional (Optional) Rear RS485 + IRIG-B Connection to a PC
2.6 Optional Rear RS232 (COM3)
The following settings, on the COMMUNICATIONS MENU, must be configured when using the electrical RS232
Com3 interface.
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......