Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 17 of 50
1.4.3.5
Electrical Fast Transient / Burst Immunity
IEC 60255-22-4 Class A (2002)
Type
Level
Variation
Case, Aux Power & I/O
4.0 kV
10 %
RS485 Metallic Comms
2.0 kV
No data loss
1.4.3.6
Surge Immunity
IEC 60255-22-5, IEC 61000-4-5
Type
Level
Variation
Analog Inputs Line to Earth
4.0 kV
10 %
Case, Aux Power & I/O Line to Earth
2.0 kV
Analog Inputs Line to Line
1.0 kV
Case, Aux Power & I/O Line to Line
1.0 kV*
RS485 Comms port Line to Earth
1.0 kV
No data loss
* Note 45ms pick up delay applied to binary inputs
1.4.3.7
Conducted Radio Frequency Interference
IEC 60255-22-6
Type
Level
Variation
0.15 to 80 MHz
10 V
5 %
1.4.3.8
Magnetic Field with Power Frequency
IEC 6100-4-8 Level 5
100A/m, (0.126mT) continuous
50Hz
1000A/m, (1.26mT) for 3s