Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Name
(Description)
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
52 W2 Line Ia
0,3
2
4
100.000
0.100
53 W2 Line Ib
0,3
2
4
100.000
0.100
54 W2 Line Ic
0,3
2
4
100.000
0.100
55 W2 Relay Ia
0,3
2
4
100.000
0.100
56 W2 Relay Ib
0,3
2
4
100.000
0.100
57 W2 Relay Ic
0,3
2
4
100.000
0.100
76 W1 I Phase A Max
0,3
2
4
100.000
1.000
77 W1 I Phase B Max
0,3
2
4
100.000
1.000
78 W1 I Phase C Max
0,3
2
4
100.000
1.000
79 W2 I Phase A Max
0,3
2
4
100.000
1.000
80 W2 I Phase B Max
0,3
2
4
100.000
1.000
81 W2 I Phase C Max
0,3
2
4
100.000
1.000
110 W1 Ia Last Trip
0,3
1
3
1.000
Disabled
111 W1 Ib Last Trip
0,3
1
3
1.000
Disabled
112 W1 Ic Last Trip
0,3
1
3
1.000
Disabled
113 W2 Ia Last Trip
0,3
1
3
1.000
Disabled
114 W2 Ib Last Trip
0,3
1
3
1.000
Disabled
115 W2 Ic Last Trip
0,3
1
3
1.000
Disabled
116 Ph-Ph V Last Trip
0,3
1
3
1.000
Disabled
117 Ig-1 Last Trip
0,3
1
3
1.000
Disabled
118 Ig-2 Last Trip
0,3
1
3
1.000
Disabled
119 CB1 Wear A
0,3
1
3
0.000
1000000.000
120 CB1 Wear B
0,3
1
3
0.000
1000000.000
121 CB1 Wear C
0,3
1
3
0.000
1000000.000
122 CB2 Wear A
0,3
1
3
0.000
1000000.000
123 CB2 Wear B
0,3
1
3
0.000
1000000.000
124 CB2 Wear C
0,3
1
3
0.000
1000000.000
5.4 Additional Settings
The following relay settings are provided for configuration of the DNP 3.0 implementation when available and are
common to all ports using this protocol.
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......