Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide
©2015 Siemens Protection Devices Limited
Chapter 6 Page 45 of 62
2.10.1 Definite Time (59NDT)
If DTL setting is small, gradually increase single phase voltage until element operates.
If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation
Apply 2x setting voltage if possible and record operating time
Phase
Vs
(Volts)
DTL
(sec)
P.U. Current
Volts
Operate Time
2 x Vs
NOTES
V
1
(V
X)
Check correct indication, trip output, alarm contacts, waveform record.
2.10.2 Inverse Time (59NIT)
It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the
Pickup Config
sub-menu in the
Output Config
menu as this will allow the Pick-up LED to operate for the function.
Gradually increase voltage until Pickup LED operates.
Apply 2x setting voltage and record operating time,
Apply a higher multiple of setting voltage and record operating time.
Compare to calculated values for operating times from:
1
1
)
sec
Vs
Vn
op
M
onds
t
Where M = Time multiplier and Vn/Vs = multiple of setting.
Ph.
Vs
(V)
TM
Operate Voltage
Operate Time
NOTES
P.U.
(Volts)
D.O.
(Volts)
2 x Vs
(sec)
x Vs
(sec)
V
1
(V
X)
2.10.2.1
Element Blocking
The Neutral Overvoltage elements can be blocked by Binary Input Inhibit. This functionality should be checked.
Element
BI Inhibits
59NIT
59NDT
Check correct indication, trip output, alarm contacts, waveform record.
When testing is complete reinstate any of the disabled functions.
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......