Section 6: Application Considerations and Examples
6.1 The Effects of An In Zone Earthing Transformer
The in zone earthing transformer is a source of zero-sequence fault current. An earth fault on the delta side of the
transformer external to the differential protection zone will cause zero sequence currents to flow in the CTs on the
delta side of the transformer without corresponding current to flow in the line CTs on the star side of the
transformer. If these zero sequence currents are allowed to flow through the differential elements they may cause
undesired tripping.
Figure 6-1: Relay Currents – External Earth Fault with In Zone Earthing Transformer
To prevent undesired tripping the ICT connections should be such as to cause the zero sequence currents to flow
in a closed delta CT secondary connection of low impedance instead of in the differential relay operating coil. As
we have already corrected for the transformer vector group on the star side a Ydy0 ICT is used on the delta side
winding.
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......