Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 33 of 50
2.11 51N Time Delayed Derived Earth Fault
2.11.1 Reference
Parameter
Value
Is
Setting
0.05, 0.1… 2.5
xIn
char
Characteristic setting
IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL
Tm
Time Multiplier setting
0.025, 0.030… 1.6, 1.7… 5, 6… 100
t
d
Delay setting
0, 0.01… 20 s
t
res
Reset setting
ANSI DECAYING, 0, 1… 60 s
2.11.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
105 %
Is
, 4 % or 1%
In
Reset level
95 %
I
op
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
f
nom
- 3 Hz to
f
nom
+ 2 Hz
5 %