Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 49 of 50
3.3 81HBL2 Inrush Detector
3.3.1 Reference
Parameter
Value
I
Setting
(Ratio of 2nd Harmonic current to
Fundamental component current)
0.10, 0.11... 0.5
3.3.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 %
I
, 4 % or 1%
In
Reset level
100 %
I
op
, 4 % or 1%
In
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
f
nom
- 3 Hz to
f
nom
+ 2 Hz
5 %
3.3.3 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
Will pick-up before operation of any protection element due
to magnetic inrush
Reset Time
Will operation until drop-off of any protection element due
to magnetic inrush