Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide
©2015 Siemens Protection Devices Limited
Chapter 2 Page 21 of 22
2.1.7
Configuring Relay Data Communication
Using the keys on the relay fascia scroll down the settings menu’s into the ‘communications’ menu. All of the
below settings may not be available in all relay types. Reydisp software is compatible with IEC60870-5-103
protocol.
COM1-RS485 Port
COM2-USB Port (Front)
COM3 – Optional Fibre Optic, RS485, RS232 or Ethernet Port
COM4 – Optional Fibre Optic Port
LAN – Optional Ethernet Ports
Setting name
Range
Default
Units
Notes
Station Address
0 … 65534
0
Address given to relay to
identify that relay from
others which may be using
the same path for
communication as other
relays for example in a fibre
optic hub
COM1-RS485 Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3
IEC60870-5-
103
COM1: Rear mounted
RS485 port
COM1-RS485 Mode
Local,Remote, Local or
Remote
Remote
COM1-RS485 Baud
Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400
19200
COM1-RS485 Parity
NONE, ODD, EVEN
EVEN
COM2-USB Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, ASCII,
DNP3
IEC60870-5-
103
COM2: Front USB port.
COM2-USB Mode
Local,Remote, Local or
Remote
Remote
COM3 Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3
IEC6-0870-5-
103
COM3: Optional rear
mounted connection
COM3 Baud Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400 57600 115200
19200
COM3 Parity
NONE, ODD, EVEN
EVEN
COM3 Line Idle*
LIGHT ON, LIGHT OFF
LIGHT OFF
COM3 Data echo*
ON, OFF
OFF
COM4 Protocol**
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3
OFF
COM4: Optional rear
mounted Fibre Optic ST
connection
COM4 Baud Rate**
75 110 150 300 600 1200
2400 4800 9600 19200
38400
19200
COM4 Parity**
NONE, ODD, EVEN
EVEN
COM4 Line Idle**
LIGHT ON, LIGHT OFF
LIGHT OFF
COM4 Data echo**
ON, OFF
OFF
DNP3 Unsolicited
Events
ENABLED, DISABLED
DISABLED
Setting is only visible when
a port protocol is set to
DNP3.
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...