Appendix 1
The operating mode of the device is set via the setting, or through a command sent to a communications port. There
are four options; Local, Remote, Local or Remote and Service.
The following table illustrates whether a function is Enabled (
✔
) or Disabled (
✖
) in each mode.
Operation Mode
Function
Local
Remote
Service
Control
Com1
✔
when Com1-Mode = Local
✔
when Com1-Mode = Remote
✖
Com2 (USB)
✔
when Com2-Mode = Local
✔
when Com2-Mode = Remote
✖
Com3
✔
when Com3-Mode = Local
✔
when Com3-Mode = Remote
✖
Com4
✔
when Com4-Mode = Local
✔
when Com4-Mode = Remote
✖
Fascia (Control Mode)
✔
✖
✖
Binary Input (n)
✔
when BI (n) Mode = Local
✔
when BI (n) Mode = Remote
✔
Binary Outputs
✔
✔
✖
Reporting
Spontaneous
IEC
✔
✔
✖
DNP3
✔
✔
✖
General Interrogation
IEC
✔
✔
✖
DNP3
✔
✔
✖
MODBUS
✔
✔
✔
Change Settings
Com1
✔
when Com1-Mode = Local
✔
when Com1-Mode = Remote
✔
Com2 (USB)
✔
when Com2-Mode = Local
✔
when Com2-Mode = Remote
✔
Com3
✔
when Com3-Mode = Local
✔
when Com3-Mode = Remote
✔
Com4
✔
when Com4-Mode = Local
✔
when Com4-Mode = Remote
✔
Fascia
✔
✔
✔
Historical Information
Waveform Records
✔
✔
✔
Event Records
✔
✔
✔
Fault Information
✔
✔
✔
Setting Information
✔
✔
✔
Fig. A1 Operating Mode Table
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......