background image

Instruction Manual IM01005031E 

Effective February 2018                   

Rev. 4

Eaton SPD Series

for Mounting External to
Electrical Distribution Equipment

Instruction Manual IM01005031E

    
Effective  November 2012           Rev. 2

Table of Contents

1.0  Introduction
2.0  Installation 
3.0  Operating Features
4.0  Troubleshooting
5.0  Specifications
6.0  Ordering Guidelines
7.0  Warranty  

Eaton SPD Series

For Mounting External To
Electrical Distribution Equipment

Summary of Contents for SPD160480D3M

Page 1: ...al Distribution Equipment Instruction Manual IM01005031E Effective November 2012 Rev 2 Table of Contents 1 0 Introduction 2 0 Installation 3 0 Operating Features 4 0 Troubleshooting 5 0 Specifications 6 0 Ordering Guidelines 7 0 Warranty Eaton SPD Series For Mounting External To Electrical Distribution Equipment ...

Page 2: ... and are intended to be installed in applications with a degree of protection rated IP 20 1 3 Safety Precautions A licensed qualified electrician must complete all instructions in this manual in accordance with the National Electric Code NEC state and local codes or other applicable country codes All applicable local electrical codes supersede these instructions WARNING IMPROPER INSTALLATION COULD...

Page 3: ...heck the facility grounding system All grounding bonding and earthing must meet the NEC and any other national state and local electrical codes 2 2 Installation Locations Eaton s SPD Series can be installed next to above or below any existing electrical enclosure The ideal mounting location for the Eaton SPD Series is as close as possible to the electrical enclosure The Eaton SPD Series should be ...

Page 4: ... state and local electrical codes when mak ing these connections Figure 2 NEMA 1 With Flushmount Suffix L 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com Determine the wire length for the Ground and Neutral 7 where applicable wires and cut these wires as needed Again keep these wires as short as...

Page 5: ...x K Figure 4 NEMA 4 4X Suffix N P 5 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 Suffix K Figure 3 NEMA 4 4X Suffix N P Figure 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment NEMA 1 Suffix K Figure 3 ...

Page 6: ...ev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect Suffix M Figure 5 NEMA 4 4X With Disconnect Suffix O Q Figure 6 6 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect S...

Page 7: ...nting External to Electrical Distribution Equipment BLUE WHITE RED WHITE ORANGE WHITE COMMON NORMALLY OPEN NORMALLY CLOSED Figure 7 Sidemount Form C Wires Figure 8 Split Phase Units Figure 9 3 Phase Delta Figure 10 3 Phase Wye Units Figure 11 High Leg Delta Units Contact Factory if High Leg is not on Phase B ...

Page 8: ...ent for each feature package Each display has both green and red light emitting diodes LEDs to indicate the status of the protection on each phase Green indicates the phase is fully protected Red indicates a loss of protection Wye Split Phase and High Leg Delta units have an additional set of green red LEDs to indicate status of Neutral Ground protection When the LEDs turn red an audible alarm wil...

Page 9: ... the display 3 Remove the two phillips head screws that hold the display 4 Rotate the display to the desired position Be careful not to overstress the display ribbon cable 5 Place the display back onto the SPD enclosure Again be careful not to overstress or crimp the ribbon cable 6 Replace the two phillips head screws Tighten screws to 1 35 Nm 12 in lbs 7 Restore power to the unit 3 3 IEC Approved...

Page 10: ...V Significant surge event Replace SPD Replace SPD with correct voltage model Check electrical system for TOV sources correct replace SPD Replace SPD One of the display Red LEDs is ON Audible Alarm is OFF Audible Alarm Silence button has been depressed and Alarm is silenced Normal operation If power is cycled and a fault condition still exists the Audible Alarm will reactivate All Green and Red LED...

Page 11: ...units 208Y 220Y 230L 240S 240D and 240H voltage codes 0 6W 400Y 480Y and 480D Basic voltage codes 1 7W 600Y and 600D voltage codes 2 1W Protection modes Single split phase L N L G N G L L Single phase L N L G N G Three phase delta L G L L Three phase Wye L N L G N G L L Three phase high leg delta L N L G N G L L Maximum continuous operating voltage MCOV 208Y 220Y 240S 240D and 240H voltage codes 1...

Page 12: ... colored LED to indicate Protection Status of the N G Mode on units with a Neutral Wire Audible alarm with Silence button Form C Relay Contact EMI RFI filtering Providing up to 50dB of Noise Attenuation from 10kHz to 100Mhz Surge Counter with Reset Button Application Suffix Options Sidemount Units K NEMA 1 Enclosure L NEMA 1 Flushmount Enclosure Available in 50 200kA Ratings Only M NEMA 1 Enclosur...

Page 13: ...rm determined by Eaton to be defec tive The giving of or failure to give any advice or recommenda tions by Eaton shall not constitute any warranty by or impose any liability upon Eaton The foregoing constitutes the sole and exclusive liability of Eaton AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY FITNESS FOR PURPOSE SOLD DESCRIPTION QUALIT...

Page 14: ...and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATIO...