U.2.25
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Installation
Jumpers
The I/O board control address has a hundreds-series prefix attached to the
control inputs and control outputs for that particular I/O board chassis slot. A
4U chassis has a 200-addresses slot for inputs IN201, IN202, etc., and outputs
OUT201, OUT202, etc. A 5U chassis has a 200-addresses slot and a 300-
addresses slot. The drawout tray on which each I/O board is mounted is keyed.
See
Installing Optional I/O Interface Boards on page 2.13
for information on
the key positions for the 200-addresses slot trays and the 300-addresses slot
trays.
Changing I/O Interface Board Jumpers
Change the I/O interface board jumpers only when you move the slot position
of an I/O board. You must remove the I/O interface boards to access the
jumpers. To change JMP1A, JMP1B, JMP2A, and JMP2B on an SEL-421
Relay I/O interface board, perform the following steps:
Step 1. Remove the relay from service. Follow your company standard
for SEL-421 for removing a relay from service. Disconnect
power from the SEL-421 Relay. Retain the GND connection, if
possible, and ground the equipment to an ESD mat.
Step 2. Remove the front panel from the SEL-421 Relay.
Step 3. Disconnect the interface board cable from the main board (the
top board).
Step 4. Pull out the drawout assembly containing the I/O interface
board.
Step 5. Locate the jumper you want to change. Jumpers JMP1A,
JMP1B, JMP2A, and JMP2B are located at the front of the I/O
board to the left and right of the interface board connector (see
,
, and
).
Step 6. Install or remove the jumper as needed. See
for
jumper position descriptions.
Step 7. Reinstall the SEL-421 Relay I/O interface board, and reconnect
the interface board cable.
Step 8. Reattach the front panel.
Step 9. Follow your company standard procedure to return the relay to
service.
Step 10. At relay power-up, confirm that the relay does not display a
Status Warning about I/O board addresses. For information on
this Status Warning, see
Relay Self-Tests on page U.6.37 in the
.
Table 2.5
I/O Board Jumpers
I/O Board
Control
Address
JMP1A
JMP1B
JMP2A
JMP2B
2XX
OFF
OFF
OFF
OFF
3XX
ON
OFF
ON
OFF
DANGER:
Disconnect or
de-energize all external
connections before opening this
device. Contact with hazardous
voltages and currents inside this
device can cause electrical shock
resulting in injury or death.
!
WARNING:
Have only
qualified personnel service this
equipment. If you are not qualified to
service this equipment, you can
injure yourself or others, or cause
equipment damage.
!
CAUTION:
Equipment
components are sensitive to
electrostatic discharge (ESD).
Undetectable permanent damage
can result if you do not use proper
ESD procedures. Ground yourself,
your work surface, and this
equipment before removing any
cover from this equipment. If your
facility is not equipped to work with
these components, contact SEL
about returning this device and
related SEL equipment for service.
!