U.1.11
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Introduction and Specifications
Specifications
UUser’s Guide
Specifications
General Specifications
AC Current Inputs (Secondary Circuits)
5 A nominal
15 A continuous,
linear to 100 A symmetrical
500 A for 1 second,
1250 A for 1 cycle
Burden:
0.27 VA @ 5 A
2.51 VA @ 15 A
1 A nominal
3 A continuous,
linear to 20 A symmetrical
100 A for 1 second,
250 A for 1 cycle
Burden:
0.13 VA @ 1 A;
1.31 VA @ 3 A
AC Voltage Inputs
300 V
L-N
continuous (connect any voltage up to 300 Vac)
600 Vac for 10 seconds
Burden:
0.03 VA @ 67 V
0.06 VA @ 120 V
0.8 VA @ 300 V
Power Supply
125/250 Vdc or 120/230 Vac
Range:
85–300 Vdc <35 W or 85–264 Vac
(30 Hz–120 Hz)
Burden:
<120 VA
48/125 Vdc or 120 Vac
Range:
38–140 Vdc <35W or 85–140 Vac
(30 Hz–120 Hz)
Burden:
<120 VA
24/48 Vdc
Range:
18–60 Vdc
Burden:
<35 W
Control Outputs
Standard:
Make:
30 A
Carry:
6 A continuous carry at 70°C
4 A continuous carry at 85°C
1s Rating:
50 A
MOV Protection
(maximum voltage):
250 Vac/330 Vdc
Pickup/Dropout Time:
6 ms, resistive load
Update Rate:
1/8 cycle
Break Capacity (10000 operations):
48 Vdc
0.50 A
L/R = 40 ms
125 Vdc
0.30 A
L/R = 40 ms
250 Vdc
0.20 A
L/R = 40 ms
Cyclic Capacity (2.5 cycle/second):
48 Vdc
0.50 A
L/R = 40 ms
125 Vdc
0.30 A
L/R = 40 ms
250 Vdc
0.20 A
L/R = 40 ms
Hybrid (high current interrupting):
Make:
30 A
Carry:
6 A continuous carry at 70°C
4 A continuous carry at 85°C
1s Rating:
50 A
MOV Protection
(maximum voltage):
330 Vdc
Pickup/Dropout Time:
6 ms, resistive load
Update Rate:
1/8 cycle
Break Capacity (10000 operations):
48 Vdc
10.0 A
L/R = 40 ms
125 Vdc
10.0 A
L/R = 40 ms
250 Vdc
10.0 A
L/R = 20 ms
Cyclic Capacity (4 cycles in 1 second, followed by 2 minutes idle for
thermal dissipation)
48 Vdc
10.0 A
L/R = 40 ms
125 Vdc
10.0 A
L/R = 40 ms
250 Vdc
10.0 A
L/R = 20 ms
Note:
Do not use hybrid control outputs to switch ac control signals.
These outputs are polarity dependent.
Fast Hybrid (high-speed high current interrupting):
Make:
30 A
Carry:
6 A continuous carry at 70°C
4 A continuous carry at 85°C
1 s Rating:
50 A
MOV Protection
(maximum voltage):
250 Vac/330 Vdc
Pickup Time:
10
m
s, resistive load
Dropout Time:
8 ms, resistive load
Update Rate:
1/8 cycle
Break Capacity (10000 operations):
48 Vdc
10.0 A
L/R = 40 ms
125 Vdc
10.0 A
L/R = 40 ms
250 Vdc
10.0 A
L/R = 20 ms
Cyclic Capacity (4 cycles in 1 second, followed by 2 minutes idle for
thermal dissipation)
48 Vdc
10.0 A
L/R = 40 ms
125 Vdc
10.0 A
L/R = 40 ms
250 Vdc
10.0 A
L/R = 20 ms
Note:
Per IEC 60255-23 (1994), using the simplified method of
assessment.
Note:
Make rating per IEEE C37.90-1989.
Control Inputs
Range:
15–265 Vdc
Accuracy:
±5% plus ±3 Vdc
Maximum Voltage:
300 Vdc
Sampling Rate:
1/16 cycle
Typical Burden:
0.24 W @ 125 Vdc
Frequency and Rotation
System Frequency:
50/60 Hz
Phase Rotation:
ABC or ACB
Frequency tracking range: 40–65 Hz
Communications Ports
EIA-232:
1 Front & 3 Rear
Serial Data Speed:
300–57600 bps
Communications Card Slot for optional
SEL-2701 Ethernet Processor
Time Inputs
IRIG Input
Input:
Demodulated IRIG-B time code
Nominal Voltage:
5 Vdc +10%
Maximum Voltage:
8 Vdc
Input Impedance:
333 Ohms
Isolation:
500 Vdc
1k PPS Input
Input:
Demodulated IRIG-B and 1k PPS
Nominal Voltage:
5 Vdc +10%
Maximum Voltage:
8 Vdc
Input Impedance:
500 Ohms
Operating Temperature
–40° to +85°C (–40° to +185°F)
Note:
LCD contrast impaired for temperatures
below –20° and above +70°C
Humidity
5% to 95% without condensation
Weight (Maximum)
3U Rack Unit:
17.5 lbs (8.0 kg)
4U Rack Unit:
21.5 lbs (9.8 kg)
5U Rack Unit:
25.5 lbs (11.6 kg)
Type Tests
Electromagnetic Compatibility (EMC)
Electromagnetic
Emissions:
EN 50263: 1999
Emissions:
IEC 60255-25 (2000)
Electromagnetic Compatibility Immunity
Conducted RF Immunity: ENV 50141: 1993,
10 V rms
Digital Radio
Telephone RF:
ENV 50204: 1995, 10 V/m at 900 MHz
and 1.89 GHz
Electrostatic Discharge:
IEC 60255-22-2 (1996),
Levels 1, 2, 3, 4
Summary of Contents for SEL-421