U.4.34
SEL-421/SEL-421-1 Relay
User’s Guide
Date Code 20020501
Basic Relay Operations
Examining Metering Quantities
=
>>
MET<Enter>
Relay 1 Date: 03/15/2001 Time: 00:00:14.938
Station A Serial Number: 2001001234
Phase Currents
IA IB IC
I MAG (A) 400.000 400.345 400.431
I ANG (DEG)
00.00 -120.10 119.90
Phase Voltages Phase-Phase Voltages
VA VB VC VAB VBC VCA
V MAG (kV)
134.001 133.999 134.001
232.095 232.093 232.097
V ANG (DEG)
00.00
-120.10 119.90 00.00 -00.10 00.10
Sequence Currents (A) Sequence Voltages (kV)
I1 3I2 3I0 V1 3V2 3V0
MAG
400.252
0.739 0.861
133.954
0.003 0.001
ANG (DEG) 0.01
-50.86 -63.65
0.00
-49.97 -120.70
A B C 3P
P (MW)
53.60 53.60 53.60 160.08
Q (MVAR)
0.00 -0.00 -0.00 -0.00
S (MVA)
0.00 0.00 0.00 0.00
POWER FACTOR
1.00 0.99 1.00 1.00
LAG
FREQ (Hz) 60.00 VDC1(V) 125.00 VDC2(V) 48.00
=
>>
Figure 4.25
Terminal Screen MET Metering Quantities.
View Metering: Terminal on page 4.31
fundamental line quantities. Other variants of the
MET
command give
different relay metering quantities. For example, you can see the line RMS
(harmonics-included) quantities by issuing the
MET RMS
command. See
Metering on page A.2.28 in the Applications Handbook
page R.8.28 in the Reference Manual
for more information on the
MET
command.
View Metering:
AC
SEL
ERATOR
Software
Use the procedures in the following steps to examine the SEL-421 Relay
metering with the
AC
SEL
ERATOR
software HMI.
This example assumes that you have successfully established communication
with the relay; see
Making an EIA-232 Serial Port Connection on page 4.6
for
a step-by-step procedure. In addition, you must be familiar with relay access
levels and passwords. See
Changing the Default Passwords: Terminal on
to change the default access level passwords. You should also be
familiar with the
AC
SEL
ERATOR
software. See
Step 1. Configure the communications port. Start the
AC
SEL
ERATOR
software. On the top toolbar, open the Communication menu,
and then click Port Parameters. You will see the Port
Parameters dialog box similar to
Speed, Data Bits, Parity, and Stop Bits that match the relay
settings. Defaults are 9600, 8, N, 1, respectively. Click OK to
update the
AC
SEL
ERATOR
software communications
parameters. Confirm that the Communications Status bar at the
bottom of the
AC
SEL
ERATOR
window says “Connected.”
Step 2. Confirm the correct
AC
SEL
ERATOR
software passwords.
Reopen the Communication menu and click Port Parameters.
Enter your Access Level 1 password in the Level One
Password text box, and your Access Level 2 password in the
Level Two Password text box. Click the OK button to accept
changes and close the dialog box.