U.4.40
SEL-421/SEL-421-1 Relay
User’s Guide
Date Code 20020501
Basic Relay Operations
Reading Oscillograms, Event Reports, and SER
Step 2. Apply power to the relay and establish communication. Start
the
AC
SEL
ERATOR
software. On the top toolbar, open the
Communication menu, and then click Port Parameters. You
will see the Port Parameters dialog box similar to
.
Select the Data Speed, Data Bits, Parity, and Stop Bits that
match the relay settings. Defaults are 9600, 8, N, 1,
respectively. Click OK to update the
AC
SEL
ERATOR
software
communications parameters. Confirm that the Communications
Status bar at the bottom of the
AC
SEL
ERATOR
window says
“Connected.”
Step 3. Confirm the correct
AC
SEL
ERATOR
software passwords.
Reopen the Communication menu and click Port Parameters.
Enter your Access Level 1 password in the Level One
Password text box, and your Access Level 2 password in the
Level Two Password text box. Click the OK button to accept
changes and close the dialog box.
Step 4. Start the
AC
SEL
ERATOR
software operator interface. In the top
toolbar HMI menu, click Meter and Control.
Step 5. View the Control Window. Click the Control Window button of
the HMI tree view. See
. The
AC
SEL
ERATOR
software displays the Control Window similar to that in
Figure 4.31
AC
SEL
ERATOR
HMI Tree View.
Figure 4.32
AC
SEL
ERATOR
HMI Control Window.