7-2 Function Code List
– Motor Parameters / Vector Control
Code
No.
Function Name
Data Content
Setting
Resolution
Factory
Presets
User
Setting
Value
Motor Parameters
5001
Motor poles, voltage and capacity
X Y ZZZ
X: Poles
Y: Rated voltage
Z: Motor capacity
—
※
1
5002
Motor current rating
0.1-999.9A
About 30
-
110% of the inverter current rating
0.1A
※
1
5003
Motor frequency rating
10
-
600Hz
1Hz
※
1
5004
Motor speed rating
0-24,000 rpm
1rpm
※
1
5005
Motor insulation type
1: Type A
2: Type E
3: Type B
4: Type F
5: Type H
1
※
1
5006
The motor’s rated voltage during auto
tuning of motor parameters
0: The voltage selected by F5001
100-460V
1V
0
5007
Rated motor slip ratio
0-50%
0.1%
2
5008
The setting of motor parameter auto
tuning range
0: No range
50-300%
0.1%
0
5009
Motor stator resistance
55kW or below
0.001-65Ω
0.001Ω
※
1
75kW or above
0.01-650mΩ
0.01mΩ
5010
Motor rotator resistance
55kW or below
0.001-65Ω
0.001Ω
※
1
75kW or above
0.01-650mΩ
0.01mΩ
5011
Motor stator inductance
55kW or below
0.1-6,000mH
0.1mH
※
1
75kW or above
0.01-600mH
0.01mH
5012
Motor rotator inductance
55kW or below
0.1-6,000mH
0.1mH
※
1
75kW or above
0.01-600mH
0.01mH
5013
Motor mutual inductance
55kW or below
0.1-6000mH
0.1mH
※
1
75kW or above
0.01-600mH
0.01mH
5014
Motor excitation current
0.01-650A
0.01A
※
1
5015
Motor inertia moment
0-65kgm
2
0.001kgm
2
※
1
5016
Load inertia moment ratio
1-200
0.01
1
5017
Iron loss resistance
0: No torque correction
0.1-6553.5Ω
0.1Ω
0
Vector control
6001
Torque limiter (power running)
Mode A
0-200%
0.1%
150
Mode B
0-150%
0.1%
120
6002
Torque limiter analog input function
(
power running)
0: F6001
1: External analog VIF1 voltage (0
-
5 V)
2: External analog VIF1 voltage
(0
-
10 V or potentiometer)
3: External analog VIF2 voltage (0
-
5 V)
4: External analog VIF2 voltage
(0
-
10V or potentiometer)
5: External analog VIF3 voltage (0
-
5 V)
6: External analog VIF3 voltage
(0
-
10V or potentiometer)
7: External analog VIF1 current (4
-
20mA)
8: External analog VIF2 current (4
-
20mA)
9: External analog VIF3 current (4
-
20mA)
1
0
6003
Torque limiter (regeneration)
Mode A
0-200%
0.1%
100
Mode B
0-150%
6004
Torque limiter analog input function
(regeneration)
0:F6003
1: External analog VIF1 voltage (0
-
5 V)
2: External analog VIF1 voltage
(0
-
10 V or potentiometer)
3: External analog VIF2 voltage (0
-
5 V)
4: External analog VIF2 voltage
(0
-
10V or potentiometer)
5: External analog VIF3 voltage (0
-
5 V)
6: External analog VIF3 voltage
(0
-
10V or potentiometer)
7: External analog VIF1 current (4
-
20mA)
8: External analog VIF2 current (4
-
20mA)
9: External analog VIF3 current (4
-
20mA)
1
0
6005
Multiple for starting excitation current
0.1
-
2 (for applicable motor)
0.01
1
6006
Starting excitation time
0: No starting excitation
0.1 -10 sec.
0.1 s
※
1