- 121 -
-
121
-
C
h
ap
ter
1
1
11-2 Inverter General Specification
11-2 Inverter general specification
Control mode
Vector control ∕ sensorless vector control ∕ V/f control
Dr
iv
in
g
p
er
fo
rm
a
n
ce
*
1
Speed
control range
With PG sensor
0.05Hz-240Hz
(
1
:
1000/50Hz reference
)
*5
Without PG sensor
0.25Hz-240Hz
(
1
:
200/50Hz reference
)
*5
Speed
Response/precision
With PG sensor
Response characteristic: 250rad/sec Precision: ±0.01%
Without PG sensor
Response characteristic: 100rad/sec Precision: ±0.5%
Torque
control range
With PG sensor
1
:
50
(
rated torque ratio
)
Without PG sensor
1
:
20
(
rated torque ratio
)
Torque precision
With PG sensor
±10%
(
of rated torque
)
Without PG sensor
±20%
(
of rated torque
)
Co
n
tr
o
l
spec
ifi
ca
tio
n
Frequency
setting resolution
Digital setting
0.01Hz
Analog setting
0.05%
(
12bit0-10V
,
4-20mA
)
, 0.1%
(
11bit0-5V
)
of the maximum output frequency
Frequency precision
Digital setting
±0.01% of output frequency
(
at -10-40
℃)
Analog setting
±0.2% of the maximum output frequency
(
at 25
℃
±10
℃)
*
2
PG input
Open collector, push-pull mode (power supply voltage 24V) Max. number of pulses:
491.52kHz
*
3
DC braking
Starting frequency (0.05-20Hz), operation time (0.1-10s), braking force (1-10 grades)
Additional functions
Restart after momentary power failure, flying start, multi-speed operation,
frequency jump, auto alarm recovery, PID control operation,
simple scheduled operation, energy-saving operation and others
O
p
er
a
tio
n
spec
ifi
ca
ti
o
n
Start/stop setting
Operation panel, serial communication (RS485, Modbus), control circuit terminals
Frequency
command setting
Digital setting
Operation panel, serial communication (RS485, Modbus),
step setting from terminal board
Analog setting
3 channels, 0-5V, 0-10V, 4-20mA, potentiometer (5kΩ, 0.3W and above)
Input signal
Frequency command, forward run command, reverse run command,
acceleration/deceleration time setting, free run stop, alarm reset, emergency stop,
jogging selection, step frequency setting, operation signal hold and others
[Digital input: 8 channels (arbitrary allocation)],
[Analog input: 3 channels for current
and voltage]
Output signal
Contact output
Alarm batch and multifunctional contact output (1C contact, 250VAC, 0.3A)
Monitor signal
Operating, frequency matching, overload alarm, undervoltge,
frequency approach and
etc.
[Open-collector output: 3 channels (arbitrary allocation), Analog output: 2 channels]
LED display
Frequency, output current, speed, load factor, no unit: (output voltage, power and etc.),
operating, alarm
LCD display
Various status, code, alarm, message display (English, Japanese, Chinese)
Communication I/F
RS485, Modbus-RTU
External power supply output
DC24V, 150mA
(
control terminal board
)
Protection function
Current limiting, overcurrent shutoff, motor overload, external thermal alarm,
undervoltage, overvoltage, momentary power failure, fin overheat, open phase
Warning function
Overvoltage prevention, current limiting during acceleration/deceleration,
brake resistor overheat, overload, overheating of radiator fins
En
v
ir
o
n
m
en
t
Ambient temperature
-10
℃
-+50
℃
(no frost):heavy overload,
-10
℃
-+40
℃
(no frost):light overload
Storage temperature
-20
℃
-+65
℃(
short-term storage during transportation
)
*
4
Relative humidity
95%RH or less
(
no condensation
)
Elevation
2000m or lower
(
Decrease the current when higher than 1000m
)
Vibration
5.9m/s
2
(
0.6G
)
or less
(
JIS C 60068-2-6 standard; IEC60068-2-6
)
Gas medium
Indoor (no corrosive or inflammable gases, oil mist, or dust)
*1
Vary with the environment, condition, motor in use or sensor.
*2
The maximum output frequency is at 5V, 10V, and 20mA.
*3
An optional board is required for linear driver input.
*4
Applicable temperature for medium-term and long-term transportation.
*5
When 2-pole motor is set, the maximum value of frequency setting range is 120Hz.
Summary of Contents for Samco SVC06
Page 1: ...High Performance Vector Control Inverter Instruction Manual Basic SANKEN ELECTRIC CO LTD...
Page 2: ......
Page 133: ...Memorandum...
Page 134: ...Memorandum...
Page 135: ......