- 81 -
C
h
ap
ter
7
-
81
-
7-2
Function Code List - Basic Operation Functions
7-2
Function Code List
Code
No.
Function Name
Data Content
Setting
Resolution
Factory
Presets
User
Setting
Value
Basic operation functions
1001
Motor control mode
selection
1: V/f control mode
2: Speed control (speed sensorless vector control )
3: Speed control (speed sensor vector control )
4: Torque control (speed sensorless vector control )
5: Torque control (speed sensor vector control )
6: Position control (speed sensor vector control )
10: Auto tuning mode 1
11: Auto tuning mode 2
40: V
•
f separation control
1
1
1002
1st speed frequency
setting selection
1: Operation panel
2: External analog VIF1 voltage (0
-
5 V)
3: External analog VIF1 voltage (0
-
10 V or potentiometer)
4: External analog VIF2 voltage (0
-
5 V)
5: External analog VIF2 voltage (0
-
10V or potentiometer)
6: External analog VIF3 voltage (0
-
5 V)
7: External analog VIF3 voltage (0
-
10V or potentiometer)
8: External analog VIF1 current (4
-
20mA)
9: External analog VIF2 current (4
-
20mA)
10: External analog VIF3 current (4
-
20mA)
11: External analog VIF1 vVIF2 voltage
12: External analog VIF1 vVIF3 voltage
13: External analog VIF2 vVIF3 voltage
14: External analog VIF1 voltage -VIF2 voltage
15: External analog VIF2 voltage –VIF1 voltage
16: External analog VIF1 voltage-VIF3 voltage
17: External analog VIF3 voltage –VIF1 voltage
18: External analog VIF1 vVIF2 current
19: External analog VIF1 voltage -VIF2 current
20: External analog VIF1 current -VIF2 voltage
21: Terminal block stepping
22: Communication
25: Pulse train input
26: External analog VIF1 forward / reverse run operation
(0
-
10V, 5V reference)
27: External analog VIF2 forward / reverse run operation
(0
-
10V, 5V reference)
28: External analog VIF3 forward / reverse run operation
(0
-
10V, 5V reference)
29: Pulse train input (subPG
:
option)
1
1
1003
V/f pattern selection
1: Linear pattern
2: Square-law decreasing pattern (weak)
3: Square-law decreasing pattern (strong)
1
1
1004
Torque boost
0-20%
(
maximum voltage ratio
)
0.1%
※
1
1005
Base voltage
200V series
0: No AVR
50-240V
1V
※
1
400V series
0: No AVR
50-460V
1006
Base frequency
0.1-600Hz
0.01Hz
※
1
The setting values can not be changed during operation.
※