11-1 Standard Specification
Item
Specification
Model
(
SVC06-□□□□-
4
)
0900
1100
1320
1600
1850
2000
2200
2500
O
u
tp
u
t
spec
ifi
ca
ti
o
n
Mode A
Heavy
overload
Standard applicable motor [kW]
90
110
132
160
185
200
220
250
Rated capacity [kVA] *1
120
146
175
211
249
267
295
327
Rated current [A] *2
173
211
253
304
360
386
426
472
Overload current rating *3
150%-1min
Output frequency range *4
0.05-400Hz
(
Starting frequency 0.05-60Hz variable)
Mode B
Light
overload
Standard applicable motor [kW]
110
132
160
200
220
250
280
315
Rated capacity [kVA] *1
146
180
211
267
295
327
374
409
Rated current [A] *2
211
253
304
386
426
472
540
590
Overload current rating *3
120%-1min
Output frequency range *4
0.05-200Hz
(
Starting frequency 0.05-60Hz variable)
Rated output voltage *5
3
φ
380V-460V
Inp
u
t
p
o
we
r
sup
p
ly
Voltage & Frequency
3
φ
380V-460V, 50/60Hz
Allowable fluctuation
Voltage: -15%, +10% Frequency: ±5% Voltage unbalance: within 3%
Power supply impedance
1% and above
(
Use optional reactor if less than 1%
)
Mode A
Heavy
overload
Required power capacity [kVA] *6
120
146
180
211
249
267
295
327
Input current
[A] *7
With DCL
161
196
235
283
335
359
396
439
Without DCL
Mode B
Light
overload
Required power capacity [kVA]*6
146
180
211
267
295
327
374
409
Input current
[A] *7
With DCL
196
235
283
359
396
439
502
549
Without DCL
Protective structure
Totally enclosed
(
IP20
)
Cooling method
Forced air cooling
Approximate weight
62kg
110kg
140kg
Carrier frequency
Sine wave PWM
(
carrier frequency 1k
-
8kHz
)
*8
DC reactor
Standard(External)
*1
Rated capacity at the output voltage of 400V
*2
When input voltage is AC400V and above, the rated current will be decreased according to the output power
*3
One minute is allowed every 10 minutes
*4
During vector control, PG sensorless is 0.25Hz
-
240Hz /PG sensor is 0.05Hz
-
240Hz (depends on the number of poles)
*5
Output voltage cannot exceed power supply voltage
*6
Vary with the impedance changes of the power supply including a DC reactor
*7
Vary with the impedance of the power supply
*8
The maximum value of carrier frequency varies with the inverter capacity mode and operation status.