- 94 -
7-2
Function Code List
– PID Function / Communication Function
Code No.
Function Name
Data Content
Setting
Resolution
Factory
Presets
User
Setting
Value
3203
External PID control selection
0: No external PID control
1: External control PID1
2: External control PID2
3: For factory adjustment
4: external controls PID1 and PID2
5: For factory adjustment
6: For factory adjustment
1
0
3204
External PID operation mode
selection
1: Operation interlocked with inverter operation
2: PID output after power input
3: PID output controlled by external terminals
1
1
3205
PID constitution selection
0: Without command value addition calculation
1: With command value addition calculation
1
0
3206
Command value addition
calculation PID control gain
0.01-100
0.01
1
3207
PID1/PID2 switching time
0.1 -6,000 minutes
0.1 minute
0.1
3301
Reading PID1 command value
Read only
1
---
3302
Reading PID1 feedback value
Read only
1
---
3303
Reading PID1 input deviation
Read only
1
---
3304
Reading PID1 output value
Read only
1
---
3305
Reading PID2 command value
Read only
1
---
3306
Reading PID2 feedback value
Read only
1
---
3307
Reading PID2 input deviation
Read only
1
---
3308
Reading PID2 output value
Read only
1
---
3309
For factory adjustment
3310
For factory adjustment
3311
For factory adjustment
3312
For factory adjustment
Communication function
4001
Message checksum
0: No
1: Yes
1
1
4003
Pull-up/down function selection
0: No
1: Yes
1
0
4004
Communication response time
1-6000ms
1ms
10
4005
Serial communication function
0:No function
1: Dedicated protocol communication function
(SANKEN communication protocol)
2: Modbus communication function
1
0
4006
Inverter No.
0
-
247
SANKEN protocol : 1
-
32
Modbus protocol : 0
-
247
1
1
4007
Communication speed
1: 1,200bps
2: 2,400bps
3: 4,800bps
4: 9,600bps
5: 19,200bps
6: 38,400bps
7: 57,600bps
1
4
4008
Parity bit
0: No
1: Odd
2: Even
1
1
4009
Stop bit
1: 1 bit
2: 2 bits
1
1
4010
End code
0: CR+LF
1: CR
1
0
4011
Specified command inverter's
response selection
0: Sent
1: Not sent (Error response sent)
2: Not sent (No error response sent)
1
0
4101
Modbus communication timeout
setting
0: No function
0.01 -600 sec.
0.01s
0
4102
Modbus communication timeout
action
0: Keep the status
1: Stop alarm
1
0
4103
Modbus register address switching
0: register number A
1: register number B
1
0