- 32 -
4-5 Composition of Control Circuit Terminals
4-5
Composition of Control Circuit Terminals
4-5-1
Wire size and terminal arrangement
Terminal screw diameter: M3
Recommended wire size 0.75 [mm
2
]
Tightening torque: 0.5[N•m]
The arrangement of control circuit terminals is as shown in the following.
A-
B+
B-
I+
ACM1
FA1
FB1
FC1
DCM1
DO1
DO2
DO3
DOE
A+
AOUT1 AOUT2
+V
VIF3
VIF2
ASG
DI4
DI5
DI6
DI7
DI8
DCM2 +24V2
ACM2
VIF1
+24V1
DI1
DI2
DI3
The common end of control circuit terminals shall not be grounded to the earth. In addition, DCM1/DCM2 shall
not be in common use with ACM1/ACM2. (Because they are insulated with each other).
Use shielded wires for wiring connected to the control circuit terminals, and connect one end of the shielding to
each common terminal or dedicated terminal, and leave the other end open. (refer to 4-3 Terminal connection
diagram).
Do not input the voltage to multifunctional terminals (DI1
-
DI8).