- 83 -
C
h
ap
ter
7
-
83
-
7-2 Function Code List - Basic Operation Functions
Code
No.
Function Name
Data Content
Setting
Resolution
Factory
Presets
User
Setting
Value
1109
Direction of motor rotation
1: Forward and reverse run
2: Forward run only
3: Reverse run only
1
1
1110
Direction of motor rotation
(Operation panel)
1: Forward run
2: Reverse run
1
1
1111
Braking method
1: Deceleration to stop
2: Deceleration to stop + DC braking
3: Free run stop
1
1
1112
DC braking start frequency
0.05-20Hz
0.01Hz
0.5
1113
DC braking time
0.1 -10 sec.
0.1 s
2
1114
DC braking force
1-10
1
5
1115
Duty cycle of brake resistor
0: No brake resistor
2-25%ED
98: No discharge resistor protection
(with discharge)
99: External brake unit
1%ED
※
1
1116
Discharge resistor on signal output
time
0.01 -10.00 sec.
0.01 s
0.1
1201
Monitor display selection
1: Frequency [Hz]
2: Output current (A)
3: Speed of rotation [rpm]
4: Load factor [%]
5: No unit display
1
1
1202
State display selection
1: No units (multiple of F1203)
2: Output voltage [V]
3: DC voltage [V]
4: Active power [kW]
5: Apparent power [kVA]
6: Radiator temperature [
℃
]
7: Command speed [rpm]
8: PID1 feedback value [Hz]
9: PID2 feedback value [Hz]
10: VIF1 analog input value [Hz]
11: VIF2 analog input value [Hz]
12: VIF3 analog input value [Hz]
13: Output torque [%]
14: Partial excitation current [A]
15: Partial torque current [A]
16: Detecting position [mm]
29: Command frequency [Hz]
30: Command torque [%]
35: Detection speed [rpm](subPG)(option)
44: Target frequency[Hz]
45: Output frequency[Hz]
1
1
1203
Multiple for no-units display
0-100
(multiple of the output frequency)
0.01
1
1301
1st jump bottom frequency
0-600 [Hz]
0.01 [Hz]
0
1302
1st jump top frequency
0-600 [Hz]
0.01 [Hz]
0
1303
2nd jump bottom frequency
0-600 [Hz]
0.01 [Hz]
0
1304
2nd jump top frequency
0-600 [Hz]
0.01 [Hz]
0
1305
3rd jump bottom frequency
0-600 [Hz]
0.01 [Hz]
0
1306
3rd jump top frequency
0-600 [Hz]
0.01 [Hz]
0
1307
Auto alarm recovery
0: No auto reset function
1: Auto reset function
1
0
1308
Instability elimination
0-20
1
0
1309
Operation direction switching in V / f
control mode
0: Start from the direction opposite to current
direction after a stop
1: Continuous operation
1
0
1315
Shortest operation time function
0 -99.99 sec.
0.01 s
0
1316
2nd Upper frequency limit
5-599 [Hz]
0.01 [Hz]
60
1317
3rd Upper frequency limit
5-599 [Hz]
0.01 [Hz]
60
1318
Cooling fan ON/OFF control
0: ON/OFF control
1: Normally ON
1
0
1319
Functions corresponding to high
altitude areas
1: 1,000m or below
2: 1,000m-1,500m or below
3: 1,500m-2,000m or below
4: 2,000m-2,500m or below
5:2,500m-3,000m
1
1
1320
Rating selection
1: Mode A (heavy overload mode) 150% 1 minute
2: Mode B (light overload mode) 120% 1 minute
1
1