- 26 -
4-4
Composition of Main Circuit Terminals
4-4
Composition of Main Circuit Terminals
4-4-1
Description of Main Circuit Terminals
Terminal
Symbol
Name
Description
R,S,T
Input power
supply terminals
Terminals connected to a three-phase commercial power supply
U,V,W
Inverter output terminals
Terminals connected to a three-phase induction motor
P,P1
DC reactor connection
terminals
Terminals connected to a DC reactor *1
P,PR
Brake resistor connection
terminals
Terminals connected to a brake resistor between P-PR
P,X
DC side
voltage terminals
Terminals connected to a brake unit
P is the DC positive terminal, X the DC negative terminal
Ground terminal
Terminal for grounding of inverter casing
*1 When connecting the reactor, please remove the jumper between P1 and P.
4-4-2
Connection Diagram of Main Circuit Terminals
(1) SVC06-0015~0075-**2/SVC06-0007-0150-*4
DC Reactor
Brake resistor
Motor
Option
(2)SVC06-0185~0300-**4
(3) SVC06-0370~0750-**4
DC Reactor
Motor
Brake resistor
Option
Internal
Option
Option
Brake unit
DC Reactor
Brake unit
Motor
Motor
Summary of Contents for Samco SVC06