- 75 -
C
h
ap
ter
6
-
75
-
6-2 Test run
Operation command values can be changed using the status of multifunctional input terminals. According to the
status of multifunctional input ROPE or RCOM, the operation commands as shown in the table below can be
selected. See F1101.
ROPE
terminal
RCOM
terminal
Operation Command
OFF
OFF
The method selected by F1101
ON
OFF
Operation Panel
OFF
ON
Communication
ON
ON
Terminal block (FR terminal or RR terminal)
6-2-8
Operation confirmation
After setting has been made by following the steps for test run, the operation shall be confirmed as follows.
Once the inverter or motor is in abnormal conditions, please stop operating immediately. See [Chapter 9 Fault
Analysis] for details.
(1) Test run steps
Please refer to the operation methods of operation panel for implementation of 5Hz operation.
Table 6-10 Test run steps
Operation
Display
1
Power supply input
2
press press
3
4
*The state where F1101 (operation command selection) is set to 1 (operation by operation panel)
①
After power input, check that the frequency ― ‖ displayed on the operation panel is flashing.
②
Set the frequency to a low frequency of about 5Hz through the quick knob . (Check that the set
frequency displayed on LED monitor is flashing)
③
Press (Drive) key to start forward running operation.(Check that the set frequency displayed on
LED monitor is flashing)
④
Press (Stop) key to stop operation of the equipment.
(2) Confirmation items during test run
Please confirm the contents listed in the table below
Table 6-11 Confirmation items during test run
Item
Result
1
Motor rotation direction
Is it the specified rotation direction?
2
Motor operation 1
Are the acceleration and deceleration smooth?
3
Motor operation 2
Is there any abnormal sound or vibration?
4
Inverter fan operation
Is the fan running?
5
Inverter display and others
Are the display on operation panel and equipment normal?
※
In the factory default configuration, fans of the inverter performs the ON / OFF control automatically by the fin
temperature of the inverter. The trial operation, set to (F1318 = 1) ON always control the fan, please check the operation of
the fan.
*When it is confirmed that there is no problem, please increase the set frequency before operation. Similarly, for the
operation with increased frequency, the above confirmation items shall also be checked.