8-2 Conflict & Interference Error
Setting function code
Error code
Description
No.
Name
Setting
3201
PID control action selection
Beyond
0
E1001
PID control action can only be used in V/f control or
speed control
E1901
Simple energy-saving mode and PID control operation
cannot be used together
1
E3203
Same PID control cannot be used both internally and
externally
2
E3203
Same PID control cannot be used both internally and
externally
4, 5
E3203
Same PID control cannot be used both internally and
externally
All
Exxxx
Cannot set analog input repeatedly
3203
External PID control selection 1
E3203
Same PID control cannot be used both internally and
externally
2
E3203
Same PID control cannot be used both internally and
externally
4, 5
E3203
Same PID control cannot be used both internally and
externally
All
Exxxx
Cannot set analog input repeatedly
5001
Motor poles, voltage and
capacity
All
Exxxx
The motor is not applicable when its capacity has a
large difference with inverter capacity
All
Exxxx
Vector control mode is only applicable to 2-, 4- and
6-pole motors
E1007/E1316/
E1317
Exceed the possible upper frequency limit
5011
Motor primary inductance
All
E5013
Mutual inductance should be smaller than primary
inductance
5012
Motor secondary inductance
All
E5013
Mutual inductance should be smaller than secondary
inductance
5013
Motor mutual inductance
All
E5011
Mutual inductance should be smaller than primary
inductance
E5012
Mutual inductance should be smaller than secondary
inductance
6002
Torque limiter analog input
function (power running)
All
Exxxx
Cannot set analog input repeatedly
6004
Torque limiter analog input
function (regeneration)
All
Exxxx
Cannot set analog input repeatedly
6015
Lower frequency limit for
motor vibration reduction
function
All
E6016
Cannot exceed the upper frequency limit
6016
Upper frequency limit for
motor vibration reduction
function
All
E6015
Cannot exceed the lower frequency limit
6101
Torque command selection
All
Exxxx
Cannot set analog input repeatedly
6103
Positive upper value of torque
command
All
E6104
Cannot exceed the lower limit value
6104
Positive lower value of torque
command
All
E6103
Cannot exceed the upper limit value
6105
Negative upper value of
torque command
All
E6106
Cannot exceed the lower limit value
6106
Negative lower value of
torque command
All
E6105
Cannot exceed the upper limit value
*
Exxxx represents analog input repetition function code.